Worldwide Free Shipping
Popular Searches:

Servo amplifier Servo motor Samsung tv board panel screen Lenovo HP x360 assembly

DVP06XA-S Delta S Series PLC Analog I/O Module AI4 AO2 new in box
  • DVP06XA-S Delta S Series PLC Analog I/O Module AI4 AO2 new in box
  • DVP06XA-S Delta S Series PLC Analog I/O Module AI4 AO2 new in box

DVP06XA-S Delta S Series PLC Analog I/O Module AI4 AO2 new in box

£86.00
Bookmark and Share
  • Description
  • Reviews
  • Shipping & Returns
Description

1. DVP06XA-S is able to receive 4 points of analog input signals (voltage or current) and convert them into 12-bit digital signals. DVP06XA-S receives 2 groups of

12-bit digital data from the PLC MPU and converts them into 2 points of analog signals for output (in voltage/current). There are 49 16-bit control registers (CR) in DVP06XA-S, and the data in it can be read and written by using FROM/TO instructions in DVP Slim series PLC MPU program.

2. The system version of DVP06XA-S can be updated via RS-485 communication. The power unit is separate from it and is small in size and easy to install.

3. The user can select voltage or current input by wiring. Range of voltage input: +-10VDC (resolution: 5mV). Range of current input: +-20mA (resolution: 20uA).

4. The user can also select voltage or current output by wiring. Range of voltage output: 0V ~ +10VDC (resolution: 2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5uA).

Specifications

Mixed analog/digital (A/D)

module

Voltage input

Current input

Power supply voltage

24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Analog input channel

4 channels per module

Analog input range

+-10V

+-20mA

Digital data range

+-2,000

+-1,000

Resolution

12 bits (1LSB=5mV)

11 bits (1LSB=20uA)

Input impedance

200KΩ and above

250Ω

Overall accuracy

+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F).

Response time

3ms × channels

Isolation method

There is no isolation between channels

Absolution input range

+-15V

+-32mA

Digital data format

2’s complement of 16-bit, (13 significant bits)

Average function

Yes (CR#2 ~ CR#5 can be set and the range is K1 ~ K4,095)

Self diagnostic function self detection

Upper bound and lower bound detection per channel

Mixed digital/analog (D/A)

module

Voltage output

Current output

Analog signal output channels

2 channel per module

Analog output range

0 ~ 10V

0 ~ 20mA

Digital data range

0 ~ 4,000

0 ~ 4,000

Resolution

12 bits (1LSB=2.5mV)

12 bits (1LSB=5uA)

Output impedance

0.5Ωor lower

Overall accuracy

+-0.5% of full scale of 25°C (77°F). +-1% of full scale during 0 ~ 55°C (32 ~ 131°F)

Response time

3ms × channels

Max. output current

20mA (1KΩ ~ 2MΩ)

/

Tolerance carried impedance

/

0 ~ 500Ω

Digital data format

2’s complement of 16-bit, (13 significant bits).

Isolation method

Isolation between digital and analog circuitry. There is no isolation between channels.

Protection

Voltage output has short circuit protection but long period of short circuit may cause internal wiring damage and current output break.

Communication mode

(RS-485)

MODBUS ASCII/RTU Mode. Communication baud rate of 4,800/9,600/19,200/38,400/57,600/115,200. For ASCII mode, date format is 7 bits, even, 1 stop bit (7, E, 1). For RTU mode, date format is 8 bits, even, 1 stop bit (8, E, 1). The RS-485 is disabled when the DVP06XA-S is connected in series with MPU.

Connect to DVP-PLC MPU

in series

When DVP06XA-S modules are connected to an MPU, the modules are numbered from 0-7. 0 is the closest to the MPU and 7 is the furthest. The Maximum number of modules is 8 modules and they do not occupy any digital I/O points of the MPU.

Power supply

Maximum power consumption

2W at 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), supplied by external power

Environment

Operation/storage

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2.

Storage: -25°C ~70°C (temperature); 5 ~ 95% (humidity).

Vibration/shock immunity

International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)
Choose a ranking for this item. 1 star is the worst and 5 stars is the best.




* Delivery Time.
We need 1-2 days to process your order before shipping.There are two shipping methoed. Fast Delivery: The delivery time for US, European countries the delivery will take 3-5 days.Slow Delivery: The delivery time for US, European countries the delivery will take 10-15 days.
* Tracking information.
After we ship package, customer receive automatic email with tracking details.
* Lost Package Policy.
If a package did not arrive in 4 weeks after the shipping date, then this package is treated as Lost. In this case a new package will be shipped to the customer provided we are able to give the same items as those purchased by the customer. If we are not able to provide the same items to substitute the lost ones we will either propose to the customer similar items or refund their cost as it will be mutually agree with the customer. If one or more items neither the same nor similar are available to be shipped, the customer can request to cancel the order entirely, thus the total cost of the order including shipping and handling cost will be fully refunded.

payment
Copyright © 2020 assemba.co.uk All Rights Reserved. Verified Manufacturers Distributor